Number of digital outputs: 2; Number of analogue outputs: 1
Measuring range
-5…100 mbar
-2…40.15 inH2O
-0.5…10 kPa
Process connection
threaded connection G 1 external thread sealing cone Attention: The unit must only be installed in a process connection for G1 sealing cone.; The G1A sealing cone of the unit is only suited for adapters with metal end stop.
Application
Special feature
Gold-plated contacts
Application
flush mountable for the food and beverage industry
Media
viscous media and liquids with suspended particles; liquids and gases
Medium temperature [°C]
-25…150
Min. bursting pressure
30000 mbar
12044 inH2O
3000 kPa
Pressure rating
4000 mbar
1606 inH2O
400 kPa
Vacuum resistance [mbar]
-1000
Type of pressure
relative pressure; vacuum
No dead space
yes
Electrical data
Min. insulation resistance [MΩ]
100; (500 V DC)
Protection class
III
Reverse polarity protection
yes
Integrated watchdog
yes
2-wire
Operating voltage [V]
20…30 DC
Current consumption [mA]
3.5…21.5
Power-on delay time [s]
< 1
3-wire
Operating voltage [V]
18…30 DC
Current consumption [mA]
5…45; (430 bei max. Laststrom)
Power-on delay time [s]
< 0.5
Inputs / outputs
Number of inputs and outputs
Number of digital outputs: 2; Number of analogue outputs: 1
Outputs
Total number of outputs
2
Output signal
switching signal; analogue signal; IO-Link
Electrical design
PNP/NPN
Number of digital outputs
2
Output function
normally open / normally closed; (parameterisable)
Number of analogue outputs
1
Analogue current output [mA]
4…20, invertible; (scalable)
Short-circuit protection
yes
Type of short-circuit protection
pulsed
Overload protection
yes
2-wire
Max. load [Ω]
300
3-wire
Max. voltage drop switching output DC [V]
2
Permanent current rating of switching output DC [mA]
100
Switching frequency DC [Hz]
125
Max. load [Ω]
(Ub – 10 V) / 21,5 mA; 650 Ω (Ub = 24 V)
Measuring/setting range
Measuring range
-5…100 mbar
-2…40.15 inH2O
-0.5…10 kPa
Set point SP
-4.9…100 mbar
-1.95…40.15 inH2O
-0.49…10 kPa
Reset point rP
-5…99.9 mbar
-2.01…40.09 inH2O
-0.5…9.99 kPa
Analogue start point
-5…80 mbar
-2.01…32.12 inH2O
-0.5…8 kPa
Analogue end point
15…100 mbar
6.02…40.15 inH2O
1.5…10 kPa
Min. difference between SP and rP
0.2 mbar
0.06 inH2O
0.02 kPa
In steps of
0.1 mbar
0.01 inH2O
0.01 kPa
Factory setting
SP1 =25 mbar
rP1 = 23 mbar
SP2 = 75 mbar
rP2 = 73 mbar
ASP = 0 mbar
AEP = 100 mbar
dAP = 2.00 s
dAA =2.00 s
Temperature monitoring
Measuring range
-25…150 °C
-13…302 °F
Accuracy / deviations
Switch point accuracy [% of the span]
< ± 0,5; (DIN EN IEC 62828-1; Turn down 1:1)
Repeatability [% of the span]
< ± 0,2; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation [% of the span]
< ± 0,5; (DIN IEC EN 62828-1 incl. zero point and span error, non-linearity, hysteresis; Turn down 1:1)
Linearity deviation [% of the span]
< ± 0,25; (Turn down 1:1)
Hysteresis deviation [% of the span]
< ± 0,2; (Turn down 1:1)
Long-term stability [% of the span]
< ± 0,1; (Turn down 1:1; per year)
Total deviation over temperature range
Temperature range
total deviation
-25…15 °C
Characteristics deviation ± 0,15 % der Spanne / 10 K
15…80 °C
Characteristics deviation
80…150 °C
Characteristics deviation ± 0,2 % der Spanne / 10 K
Notes on the accuracy / deviation
for further details see section Diagrams and graphs
Temperature monitoring
Accuracy [K]
± 2,5+ (0,08 x ( Umgebungstemperatur – Mediumtemperatur ))
Repeatability [K]
± 0,2
Resolution [K]
0.2
Response times
Damping process value dAP [s]
0…99.99
Damping for the analogue output dAA [s]
0…99.99
2-wire
Step response time analogue output [ms]
30
3-wire
Min. response time of switching output (dAP) [ms]
3
Step response time analogue output [ms]
7
Temperature monitoring
Dynamic response T05 / T09 [s]
< 35 / < 135; (DIN EN 60751 water ; > 0,9 m/s)
Interfaces
Communication interface
IO-Link
Transmission type
COM2 (38,4 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9
Profiles
Identification and Diagnosis (0x4000), Measurement Data Channel (0x800A)
threaded connection G 1 external thread sealing cone Attention: The unit must only be installed in a process connection for G1 sealing cone.; The G1A sealing cone of the unit is only suited for adapters with metal end stop.
Displays / operating elements
Display
Display unit
LED, green
switching status
LED, yellow
function display
alphanumeric display, 4-digit
measured values
alphanumeric display, 4-digit
Display unit
mbar; kPa; inH2O
Remarks
Pack quantity
1 pcs.
Electrical connection
Connection
Connector: 1 x M12; coding: A; Contacts: gold-plated
Diagrams and graphs
X
temperature
Y
total deviation